Most commercial insurance policies do not name an electrical certificate, but they expect you to show the fixed wiring has been inspected and maintained, and a commercial EICR is the standard way to do that. It also helps you meet your duty under the Electricity at Work Regulations 1989.
Do insurers actually ask for this?
Not always upfront. If a claim involves a fire or an electrical fault, though, an insurer may ask for evidence that the installation was maintained, and without a current report that is a hard question to answer. Policies vary in how explicit they are, so read your own wording or ask your broker. A commercial lease can carry its own separate requirement on top of the policy.
What does the law say?
The Electricity at Work Regulations 1989 require electrical systems to be maintained so as to prevent danger, as far as reasonably practicable. They do not name a fixed testing interval, but periodic inspection and testing is the accepted way to show you are doing it. Employers and the self-employed are covered, and landlords of commercial buildings often pass the duty to tenants through the lease.
What counts as evidence of an electrical inspection?
A commercial EICR from a competent person, covering the fixed wiring, distribution boards and circuits across the premises. It is a written report, not a verbal sign-off. Observations are coded C1 (danger present, immediate action needed), C2 (potentially dangerous), C3 (improvement recommended) or FI (further investigation advised). Since BS 7671 Amendment 4 in 2026, only C1 and C2 make a report unsatisfactory.
How often does a business need one?
BS 7671 requires the report to state a recommended date for the next inspection, and the interval depends on how the building is used and maintained. The IET’s guidance gives typical starting points: up to 5 years for offices, shops and most commercial premises, and around 3 years for industrial units and similar. Some places need it more often, such as swimming pools and caravan parks (yearly) and construction sites (every 3 months). Your electrician should confirm the interval for your premises on the report.
What if my lease or policy does not specify?
Many do not state a certificate requirement. That does not mean it will not matter. Landlords, lenders, brokers and auditors can all ask for evidence at short notice, and a business with nothing on file is in a worse position than one that can produce a current report straight away.
What should you keep on file?
- The EICR itself and the date it was carried out.
- The recommended date of the next inspection.
- Confirmation that any C1 or C2 observations were put right, with the remedial certificate.
Keeping these together means you are not hunting for them when a broker or auditor asks.
Common questions
Is an EICR a legal requirement for a business?
There is no law that says “have an EICR”, but the Electricity at Work Regulations 1989 require you to keep the installation safe, and an EICR is the usual proof.
Does the report cover portable appliances?
No. PAT testing is separate from fixed wiring inspection.
We are NICEIC approved, CHAS accredited and Gas Safe registered, and we carry out commercial inspections across offices, shops and warehouses in Manchester. See our commercial EICR service, or read why electrical compliance matters for Manchester businesses for the wider picture. Book online to get a current report on file.